Important Product Information 21
GFK-1671P
Problems Resolved by Version 2.03
Hardware issues resolved:
24498
VersaPro incorrectly reports a fatal overlap when configured for %GB,%GC,%GD &
%GE references for BEM731
Details: VersaPro 2.02 erroneously indicates a fatal overlap when a Genius Bus Controller
IC697BEM731 is configured to receive global data from two other 90-70 GBCs. The first 90-
70 global data is configured to go to %GB0001 length 64 bits and the second 90-70 global
data is configured to go to %GC0001 length 64. These are two distinct memory areas but
VersaPro erroneously indicates that there is a fatal overlap.
Resolution: This has been corrected in VersaPro 2.03 and no fatal overlap is reported.
24636
Verify of VersaMax Ref Memory Alloc says Equal even if they are not
Details: Store a default VersaMax configuration with any CPU and verify. Verify is equal as
expected. Now change the memory limits in CPU Memory tab to value other than the defaults.
VersaPro reports that the Reference Memory Alloc data is still equal on Verify.
Resolution: This has been corrected in VersaPro 2.03 and Verify works correctly.
25334
Power consumption values gets changed if port mode for VersaMax CPUs is changed
Details: Changing the port mode in VersaMax CPU configuration changes the power
consumption values for the CPU. These values should not get changed by changing the port
modes.
25473
Incorrect description for VersaMax Expansion Bus Transmitter in HWC print report
Details: HWC report of a VersaMax rack with an VM Expansion Bus Transmitter
(IC200ETM001) says "IC200ETM001 Expansion Bus Isolated Receiver".
Resolution: Description has been changed in VersaPro 2.03 to print "IC200ETM001
Expansion Bus Transmitter".
26251
Incorrect module dependant data for VersaMax Analog modules
Details: The 16-bit module dependant data in the Hardware configuration was incorrect for
VersaMax Analog modules.
Resolution: This is corrected in VersaPro 2.03.
22975
Printing HWC report of configuration having Profibus Master modules locks up the
application.
Details: If you try to print or view print preview of a HWC configuration with any Profibus
Master module, the HWC application locks up and will have to be terminated through the
Windows task manager
Resolution: This is fixed in VersaPro 2.03 and Print works as expected.
23171
HWC Reference View manager contains incorrect slot locations for VersaMax modules
Details: HWC Reference View Manager lists incorrectly the slot locations of references for
VersaMax modules. The slot locations are off by 1.
Resolution: This problem has been corrected in VersaPro 2.03
Blank data areas in between used ones may lead to corruption in Profibus Master
module configuration
Details: If a Profibus Master module configuration has unused data areas in between used data
areas, it may cause corruption of the Profibus configuration.
Resolution: Any such blank data areas are automatically deleted on save in VersaPro 2.03.
25945
VersaPro does not flag an error is Subnet Mask or Gateway IP address is set to non-zero
values when IP address is 0.0.0.0
Details: In the Ethernet tab of HWC configuration of Series 90-30 CPU364/CPU374, Series
90-70 CMM741/742 and VersaMax E05, no error is reported if Subnet Mask or Gateway IP
address is set to non-zero values when IP address is 0.0.0.0.
Resolution: VersaPro 2.03 reports an error in case of such a configuration.