44 Important Product Information
GFK-1671P
Open Issues and Problems
ID Description
CR73149
VersaPro 1.0 appears non-functional if login profile used with Nano/Micro Edition.
Details: If the Default Hardware Configuration was set to 90-30 Low End in VersaPro 1.0,
after upgrading to VersaPro 1.1, when you create a new folder, you will get the message
“Cannot Create Hardware configuration” and the folder will not be created.
Resolution: Changing the Default Hardware Configuration setting fixes this problem. (From
the Tools menu, select Options. On the General tab in the Options dialog box, select a default
hardware type from the Default Hardware Configuration list.)
CR73136
VersaPro Install problem when logged onto a Novell network.
Details: When attempting to install VersaPro when also logged onto a Novell network, the
following errors will be reported:
RUNDLL has performed an illegal operation and will be shutdown
NWPOPUP has performed an illegal operation.......
MSGSRV32 " "
ESSVC " "
MNTASK " "
Installation aborted
Resolution: You should re-boot the computer and not log onto a Novell network. VersaPro
will then install successfully.
CR75738
Unable to connect to PLC through VersaPro when FrameworX is also installed.
Details: After installing VersaPro, FxView, FxControl, and FxMotion attempt to connect to
any PLC through VersaPro. An error message is presented and connection is not successful.
Steps To Reproduce:
1.Install and authorize VersaPro
2.Install FxView, FxControl and FxMotion.
3.Open VersaPro and attempt to connect to any PLC.
The following error is presented: “Unable to establish RTU communications.” and PLC
connection fails.
Resolution: FrameworX registers an older version of opcproxy.dll. This problem can be
worked around by re-registering the opcproxy.dll using the following command from a
command window:
regsvr32 opcproxy.dll
Information Window Issues:
ID Description
CR71367
Information Window Scroll Bar Issue.
Details: In the Information window the following incorrect characteristic exists.
When an Information Window is resized to a larger window, the slider bar/button in the slider
area on the right hand side of the display grows to the point it cannot be not be moved up and
down. It, therefore, cannot be used to scroll the window (and there is information that can’t be
seen on the screen). The arrow buttons are the only method to scroll the window.
Resolution: The window can be re-sized or the arrow keys can be used to see the information
not in view.