Open Issues and Problems
Internationalization Issues:
ID Description
CR73556
Can’t create configuration for CMM321 when regional settings are Swedish or if
decimal separator is different than a period.
Details: When using VersaPro with Windows 95/NT Regional Settings other than American
English or using a decimal separator other than a period, there are problems in configuring
some modules in hardware configuration because VersaPro converts the parameter strings with
decimals into numbers that are out of range. This prevents the user from being able to
configure some modules.
Resolution: The work around is to use English (United States) with the default decimal
separator as a period or use a period as a decimal separator if a regional setting other than
English (United States) is used. This is changed in the Windows operating system by
selecting: Start
®Settings®Control Panel®Regional Settings®Number®Decimal symbol.
LD Editor Issues:
ID Description
CR73940
Save As Bitmap Loses Text Within Coil if animating.
Details: Select a portion of user logic (LD) that is online, equal to the PLC, and animating.
Perform a Copy As ® Bitmap operation. Paste the bitmap into a target application such as
Word. In some instances, the contents of the Coil (I.e. a Reset coil) will be missing.
Resolution: You should do this type of copying when off-line to avoid this problem.
CR74288
Fatal fault after copy/paste/save with many blank lines at the end of block.
Details: Copy the last rung of a block that contains greater than 1200 blank lines after the last
valid rung of logic. Paste it at the end. Press the Save Icon and VersaPro will crash.
Resolution: You should delete blank lines at the end of a block before pasting at the end of
the block..
CR75069
Changes to existing comments lost when loading from PLC.
Details: Create a new folder and create some comments. Store the folder to the PLC. Make
modifications to the existing comments and save the changes in VersaPro. Load from the
PLC. The changed comments are deleted and the comments revert to the original comments.
Resolution: If you do a check all before loading from the PLC, the changed comments are
preserved.